Interpretation #7534
Published July 15, 2015
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 9
- Section
- 903.2.8
- Topic
- 13R Fire sprinkler coverage
Question
Is it the intent of this section to require sprinklers throughout a building protected in accordance with NFPA 13R even in areas where NFPA 13R permits sprinklers to be omitted?
Answer Published 07/15/2015 at 12:36 PM
No. The intent is to have the sprinkler system installed in
accordance with the appropriate standard.
accordance with the appropriate standard.
Commentary
None