Interpretation #7534

Published July 15, 2015

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
9
Section
903.2.8
Topic
13R Fire sprinkler coverage

Question

Is it the intent of this section to require sprinklers throughout a building protected in accordance with NFPA 13R even in areas where NFPA 13R permits sprinklers to be omitted?

Answer Published 07/15/2015 at 12:36 PM

No. The intent is to have the sprinkler system installed in
accordance with the appropriate standard.

Commentary

None