Interpretation #7530

Published July 15, 2015

Original Request

Code Version
2014
Code
RESIDENT
Code Description
Chapter
Section
Flood elevation
Topic
Appliances below BFE

Question

Is it the intent of the code to raise washer, dryer, water heater above flood criteria to what elevation?

Answer Published 07/15/2015 at 12:33 PM

Yes.

Commentary

The requester does not indicate if this is an enclosed area, but we assume that it is as washers and dryers are not typically placed in open areas. The placement of electrical appliances below the design flood elevation is prohibited. The use of enclosed areas below the design flood elevation is limited to parking, building access, or storage per Section R322.2.2. Further, the code prohibits the placement of plumbing appliances below the design flood elevation unless they are designed for such locations. In R322.1.6, The definition of plumbing appliance specifically includes clothes washers and water heaters. Protection of the electrical system would encompass not placing a clothes dryer in such a location. As to the required elevation, the answer is above the Design Flood Elevation (DFE).