Interpretation #7526

Published July 07, 2015

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1010
Topic
Sidewalk slope

Question

According to Chapter 10, specifically sections 1010.2 - Slope, is it allowable to construct a sidewalk/ramp with a running slope less than 12.5%?

Answer Published 07/07/2015 at 8:37 AM

1010 is for ramps that are used as a component of a means of
egress, the situation described is not a component of a
means of egress.

Commentary

A flatter slope is not only allowed but encouraged in all regulated locations. 11% is lower/flatter than 12.5%