Interpretation #7525

Published July 07, 2015

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1008.1.1 and 1008.1.2
Topic
Glass sliding doors in health care

Question

Is it the intent of the code to require the clear opening of the sliding panel to meet the minimum opening width of 41 1/2 inches even when the door breakaway feature when opened will provide the complying opening width?

Answer Published 07/07/2015 at 8:36 AM

No, for this specific case.

Commentary

The breakaway feature hardware - for the trained personal working in an ICU is "readily openable ... without the use of a key or special knowledge". Although the 1008.1.9.5 states "unlatching of any door or leaf shall not require more than one operation", (and the description of the system indicates two operations are necessary (open the first door, push the 2 doors)) - 1008.1.4. although it is titled "Power-operated doors", recognizes 2 operations are necessary to open the 2 leafs of the breakout door. Please note: The requestor notes the doors swing into the room (emergency entry into the ICO), however the code speaks of egress - swinging out. This should be addressed with the AHJ.