Interpretation #7522

Published July 07, 2015

Original Request

Code Version
2014
Code
BUILDING
Code Description
Chapter
Section
MEANS OF ESCAPE
Topic
Other than means of egress

Question

Is it the intent of defining a "Means of Escape" to supplement only 1008.1.4.5? (Protective devices for emergency escape and rescue openings)

Answer Published 07/07/2015 at 8:35 AM

No.

Commentary

The definition of means of escape applies solely to the provisions of 1008.1.4.6. It is not intended to be used in any other manner than in conjunction with the temporary protection of emergency escape and rescue openings. Section 1008.1 indicates doors for egress that are in numbers greater than required by the code are still required to meet the provisions of Section 1008.1 for doors.