Interpretation #7507

Published June 01, 2015

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
4
Section
412.4.6
Topic
Hangar foam suppression

Question

Is the intent of section 412.4.6, exception to eliminate the requirement of foam suppression in a Group II hangar utilized for storage of an aircraft without any maintenance being performed in this facility?

Answer Published 06/01/2015 at 1:13 PM

No, not with the question worded as is. The intent of the
exception is to eliminate the requirement for a foam
suppression system only when all requirements of the
exception are met.

Commentary

The Exception is very specific in its application and does not address private hangars, but those operated by a Fixed Base Operator (FBO). There may be other avenues provided by NFPA 409. This section permits repair facilities to store aircraft that are awaiting parts, space to get in the repair shop, or payment, in a separate hanger. This provides relief from the foam requirement for these hangers since only short term storage occurs there, and no maintenance.