Interpretation #7499

Published May 19, 2015

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1018
Topic
Rating of corridors

Question

Is it the intent of 1018.1 to require rating of open corridors, hallways, passageways in B Use (without sprinklers)regardless of whether the corridor is enclosed or the length of Exit Access Travel Distance?

Answer Published 05/19/2015 at 8:05 AM

Yes, it is the intent to require all "corridors" to be fire
rated in a non-sprinklered building when the occupant load
exceeds 30 unless meeting exception 4.

Commentary

A corridor is defined as an enclosed component of a means of egress - see 1002.1. If it is not enclosed, it is not a corridor and may have other requirements. See 1018.6 for reception areas.