Interpretation #7499
Published May 19, 2015
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 10
- Section
- 1018
- Topic
- Rating of corridors
Question
Is it the intent of 1018.1 to require rating of open corridors, hallways, passageways in B Use (without sprinklers)regardless of whether the corridor is enclosed or the length of Exit Access Travel Distance?
Answer Published 05/19/2015 at 8:05 AM
Yes, it is the intent to require all "corridors" to be fire
rated in a non-sprinklered building when the occupant load
exceeds 30 unless meeting exception 4.
rated in a non-sprinklered building when the occupant load
exceeds 30 unless meeting exception 4.
Commentary
A corridor is defined as an enclosed component of a means
of egress - see 1002.1. If it is not enclosed, it is not a
corridor and may have other requirements. See 1018.6 for
reception areas.