Interpretation #7491

Published May 12, 2015

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
18
Section
1807.3.2.1
Topic
Lateral vs vertical soil presuure

Question

Is it the intent of Equation 18-1 to determine a final 'd' and not be used in conjunction with other foundation formulas? Specifically, you cannot have PART of the overturning moment be resisted by LATERAL soil pressure via this embedded post formula and then the remaining amount of overturning moment be resisted by VERTICAL soil pressure at the bottom of the footing using a typical shallow footing calculation (resultant within middle third etc.), correct?

Answer Published 05/12/2015 at 10:11 AM

Engineering formulas and calculations allow for a variety
of calculation methods depending on the specific site
conditions and methods being used. Without a soils report
and in depth investigation, it is not likely a specific
answer can be given at this time. The engineer of record
should be consulted and requested to provide the
information. If that is still unsatisfactory to the
questioner, a peer review could be used to evaluate the
method of calculation used.

Commentary

None