Interpretation #7451

Published March 18, 2015

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
2
Section
202
Topic
Increased fire area as addition

Question

Is it the intent of section 202.1 FEBC, definition of addition, to include an increase in fire area in the definition of addition?

Answer Published 03/18/2015 at 8:42 AM

No. See the attached commentary

Commentary

As defined by section 202, to be an addition, the expansion would need to increase floor area, number of stories or the height. The building code does not define an increase in fire area as an addition. In a case as described above, work closely with the local fire marshal to determine the sprinkler requirements, in this case, they may be more restrictive.