Interpretation #7445

Published February 27, 2015

Download Final PDF

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
6
Section
607.3.3.2
Topic
Smoke damper control

Question

Is it the intent of 607.3.3.2, exception 4 to allow any smoke damper located in a duct at a penetration of a corridor wall to be actuated by a corridor smoke detection system and alleviate the requirement for a duct smoke detector within 5 feet of the damper, regardless of where the inlets/outlets connected to that duct are located?

Answer Published 02/27/2015 at 2:58 PM

FMC 607.3.3.2, Method 4, allows the use a smoke detection
system installed in a corridor OR a total coverage system
in the building to control a smoke damper installed in a
corridor wall or ceiling.

Commentary

The charging paragraph states per 907.3 and ONE of the following conditions. When invoking Item 4, Item 1 is not applicable.