Interpretation #7444

Published February 27, 2015

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
507.2.1
Topic
Wood burning pizza oven hood

Question

Is it the intent of 507.2.1 to require wood

burning pizza ovens to be installed under a Type

1 hood if the pizza oven is a clay type with a

masonry or brick chimney/vent?

Answer Published 02/27/2015 at 2:56 PM

No. The mechanical code does not include
brick or clay ducts as an option for
metal ducts.

Commentary

While FMC 506.3.1.1 is specific as to what materials may be used to serve a Type I hood, brick or clay are not included. It is possible the answer could be yes. The code intent is to require a Type I Hood. The code is specific that Type I hoods are to be of steel and does not provide any alternate, although a building official could accept an alternate shown to be the equivalent or better, such as brick or clay, with proper documentation, although the porous nature of clay or brick could present a problem in establishing equivalency.