Is it the intent of section 307.2.2 to require
condensate pvc pipe joints to meet FBC-P section
705.14
Interpretation #7442
Published January 28, 2015
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 3
- Section
- 307.2.2
- Topic
- Condensate drains
Question
Answer Published 01/28/2015 at 3:11 PM
For the joints in the piping, the answer is yes. You make
a comment regarding the condensate going into a gutter.
this may may be the "approved place of disposal" addressed
in 307.2.1 which would be an indirect waste.
a comment regarding the condensate going into a gutter.
this may may be the "approved place of disposal" addressed
in 307.2.1 which would be an indirect waste.
Commentary
None