Question
Is it the intent of the code to require mechanical ventilation at all times or only during occupied conditions and is the ventilation during normal occupied times for temperature control (see 1105.6.3.2) or for proper indoor air quality (see 1105.6.3.1)?
Answer Published 12/15/2014 at 10:04 AM
No. Please see the attached commentary.
Commentary
The ventilation requirements in Section 1105 are intended
for machinery rooms. For normal operation, (1) no less than
0.5 cfm per square foot of machinery room area or (2) 20
cfm per person are required. The greater of the two shall
be provided during occupied conditions.
Normal ventilation is required only when the room is
occupied. If the equipment room is not normally occupied,
normal ventilation should be interlocked with the room
lighting. If the equipment room is constantly occupied, the
normal ventilation must be continuous.
Additionally, sufficient ventilation must be provided to
limit the machinery room temperature rise to 18°F taking
into account the ambient heating effect of all machinery in
the room. This may be the more challenging part of the
design since the heat created by running the equipment
would have to be anticipated when designing the system