Interpretation #7435

Published December 15, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
6
Section
601.4
Topic
Balance air and undercut doors

Question

Is it the intent of 601.4 exceptions 1 and 2 to require the door to be undercut when already requiring properly sized transfer grills to achieve balanced return air?

Answer Published 12/15/2014 at 10:04 AM

Yes to the question and No to the comment.

Commentary

When this code section was proposed in order to achieve close to the 0.01 W.C. across closed doors, the equivalent cross sectional duct area for a transfer duct would be approximately twice the size of the supply duct. The 1” undercut door was introduced to the code in an effort to provide additional square inches for return air. By doing this, the return duct cross sectional area was reduced to 1- 1/2 times the supply duct and transfer grills were reduced to 50 sq. in. per 100 c.f.m.