Interpretation #7433

Published December 10, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R302.5
Topic
Attic access in garage

Question

Is it the intent of the Florida Building Code - Residential section R302.5 to allow for the installation of an attic access or drop down ladder for attic access in the ceiling of the garage when the ceiling is used as the means for separation of the residence from the garage?

Answer Published 12/10/2014 at 11:24 AM

Table R302.6 stipulates the required separation from a
garage to the residence and attics as not less than 1/2
inch drywall, if the pull down ladder meets or exceeds the
1/2 inch drywall requirement then it would be permitted, if
not, no.

Commentary

We also must remember, this answer may depend on the specific conditions. If the space above the garage is attic open to attic above the rest of the house, such as may be the case in a one story structure with an attached garage, it is possible. If there is living space above the garage, it is umlikely there would be enough space to even consider the application as stated. This condition is not adddressed here.