Interpretation #7432

Published December 10, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
24
Section
G2403(202)/G 2420.2 (4)
Topic
Gas service shut off valve

Question

The following questions pertain to single family residential homes. 1. Is it the intent of the G 2403(202) Definitions be an enforceable section of the code? 2. Is it the intent of the Residential Code to require a service shutoff valve at the outlet of the serving gas suppliers meter or regulator (customer owned piping) in addition to the service shutoff valve installed at the supply inlet by the serving gas supplier (i.e. the shutoff located at the meter or regulator)?

Answer Published 12/10/2014 at 11:22 AM

1) Definitions are just that, they define a word or group
of words to help us all apply the rules, they are not
requirements.

2) No, a service shut off valve is not required, in
addition to the meter valve.

Commentary

None