Interpretation #7426

Published November 25, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1008.1
Topic
Painting egress doors and frames

Question

Is it the intent of 1008.1 that egress doors and frames shall not be painted flat black to match adjacent walls? This has an impact affecting easy recognition.

Answer Published 11/25/2014 at 1:55 PM

Means of egress doors shall be readily distinguishable
from the adjacent construction and finishes such that the
doors are easily recognizable as doors.

Can you easily tell its a door? Please see the attached
commentary for additional information.

Commentary

The issue is the door, not the frame. The following is only for the means of egress door as stated in section 1008.1- Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials.