Interpretation #7419
Published October 30, 2014
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 13
- Section
- 503.2.2
- Topic
- Unit sizing using sensible and/or latent
Question
While the chapter states 13, this question is related to the FBC - Energy Conversation Volume. Is it the intent of section 503.2.2 to limit the cooling capacity of the cooling equipment to less than the calculated sensible load?
Answer Published 10/30/2014 at 7:47 AM
Assuming that the Code in question is the 2010 Energy
Efficiency Code, Chapter 5, Section 503.2.2, the answer to
the question is, "no."
Efficiency Code, Chapter 5, Section 503.2.2, the answer to
the question is, "no."
Commentary
The 2004 Energy Code defined the equipment selection point
to be between 100% and 120% of the sensible load. As the
requester points out, this usually meant that the total
selected cooling capacity did indeed exceed the total load
requirements. In 2007 this verbiage was changed to
something more similar to the 2010 verbiage which requires
that the equipment capacity "not exceed" the heat load
calculation, but no tolerance is given. There is also no
elaboration on whether this limit refers to sensible,
latent or total loads, so it's the designer's option to
either, "not exceed" the sensible load or "not exceed" the
total (sensible + latent) load. Section 503.2.2, Exception
No. 3 provides some relief. The designer may choose
to "not exceed" but still meet the sensible load. Assuming
the use of unitary equipment or water-source heat pumps and
barring a fantastically improbable selection coincidence
where the proposed equipment meets the loads exactly, under
Exception No. 3, the selected equipment sensible capacity
will exceed the sensible load. For the described
application it is certain that the selected equipment total
capacity will also exceed the total heat load.