Interpretation #7417

Published October 27, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
5
Section
504.2
Topic
Height limit of R-2 Type V-A

Question

Is it the intent of 504.2 to limit the height of an R-2 occupancy with VA construction and automatic sprinkler system to four stories.

Answer Published 10/27/2014 at 1:19 PM

Concerning the FBC, for an R-2 with Type VA construction,
Table 503 limits you to 3 stories. With either a 13R or a
full 13 system, you can go to four stories.

Commentary

The differnce would be if you were dealing with a 4 story limit in Table 503, like for a Type IV building. Then you could only go four stories with 13R but you could go 5 stories with a full 13 system.