Interpretation #7416
Published October 27, 2014
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 10
- Section
- 1018
- Topic
- Group B exit requirements
Question
Is it the intent of Section 1018, Table 1018.1 to allow the occupant load serving a corridor to be split between exits in the case that there are three of more exits provided for a 'B' occupancy in an unsprinklered building so that neither a 1-hour rated corridor or a sprinkler system is required?
Answer Published 10/27/2014 at 1:18 PM
No.
Commentary
Table 1018.1 says "occupant load served by corridor". This
is independent of the number of occupants going to each
stair.