Interpretation #7411

Published October 21, 2014

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
24
Section
2411.3.2.1
Topic
Door assembly water infiltration

Question

Is it the intent of Section 2411.3.2.1 Exception #1 to require door assemblies only installed in "Habitable Areas/Spaces" (as defined by the Florida Building Code) to comply with water infiltration requirements?

Answer Published 10/21/2014 at 2:29 PM

No. Please see the attached commentary

Commentary

It is the intent of the referenced section to exempt areas which are designed and otherwise make provisions to allow water infiltration into the space. Tropical cyclones produce significant rainfall and often this rainfall occurs horizontally due to associated elevated winds. Office, assembly, storage and retail occupancies spaces are typically not designed with impermeable surfaces, contents and finishes that do not become damaged due to water that infiltrates. Don't ignore the requirement contained in the Exception that requires the areas to be nonhabitable AND designed to accept water infiltration. Offices, assemblies, storage, retail and other occupancies are not typically designed to accept water infiltration.