Interpretation #7410
Published October 21, 2014
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 7
- Section
- 710 and 713
- Topic
- Smoke Barrier in Type VA
Question
Is it the intent of section 710.4 in a Type VA building, constructed of wooden roof trusses that are part of a one-hour rated ceiling roof assembly, to permit a one-hour fire rated smoke barrier to intersect the wooden roof truss at a right angle so that the wooden roof truss penetrates the smoke barrier as the smoke barrier tracks through the one-hour fire rated ceiling assembly to the roof deck above?
Answer Published 10/21/2014 at 2:29 PM
No. In type VA the smoke barrier must be supported by a
rated assembly. It would stop at the bottom of the rated
roof/ceiling assembly.
rated assembly. It would stop at the bottom of the rated
roof/ceiling assembly.
Commentary
If the application has been tested in the configuration
described, it will have a design number and specifics for
the construction. The penetrations contemplated by the code
are pipes, tubes, conduit and the like. In this case, the
penetration is by a structural member. The smoke barrier is
required to be supported by construction with the same fire
resistance rating as the smoke barrier.