Interpretation #7409

Published October 21, 2014

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
7
Section
710 and 713
Topic
FRTW and smoke barriers

Question

Is it the intent of section 710.4 in a Type IIB building constructed of FRTW roof trusses to permit a one hour fire rated smoke barrier to intersect a FRTW roof truss at a right angle so that the FRTW roof truss penetrates the smoke barrier as the smoke barrier tracks to the roof deck above?

Answer Published 10/21/2014 at 2:28 PM

No, unless the assembly has been tested in the end use
described.

Commentary

710.4 allows for non-rated support of the wall. But, the penetration must comply with 713.3.1.1 OR 713.3.1.2. If the fire caulk manufacturer has tested this assembly exactly as installed, then it could be permitted. If not, an opinion letter with supporting test data from the manufacturer's engineers might be used to justify an application for an alternate method and material. Note: Vertical restraint of trusses should not take place without approval of the truss design engineer.