Interpretation #7404

Published October 08, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
1
Section
306.5.1
Topic
Working platform and guardrails

Question

Is it the intent of this section to assure that an appliance (range hood fan) mounted on the roof of a residence, have a level service platform with guardrails?

Answer Published 10/08/2014 at 8:52 AM

While it is true that Residential Code Section 1301.1
directs the reader to the Florida Mechanical Code, the
section that requires level workspaces and guardrails is
Section 306.5 (not 305.5.1). In that section, there is an
exception that states, "This section shall not apply to
Group R-3 occupancies." Section 306.5.1 is subordinate to
306.5 so its requirements do not apply in R-3 occupancies.
If the residence is an R-3 (single-family home), no such
platform with guardrails is required.

Commentary

None