Interpretation #7403

Published September 26, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
4
Section
403.2.1
Topic
Outside air requirement

Question

Is it the intent of section 403.2.1 (#3) to require 100% outside air unit for all commercial kitchens?

Answer Published 09/26/2014 at 8:43 AM

No

Commentary

Section 403.2.1, #3 states, "...recirculation from such spaces shall be prohibited." and, "All air supplied to such spaces shall be exhausted..." It does not say "...recirculation within such spaces shall be prohibited." Nor does it say, "All air supplied within such spaces shall be exhausted." It is permissible to have cooling equipment within a kitchen that recirculates air within that kitchen as long as the required exhaust and makeup air balance does not result in air being returned to adjacent spaces. As a corollary, all air being delivered to the kitchen from an adjacent space must be exhausted simply because it can't be returned to the adjacent space. It does not necessarily follow that all the supply needs to be 100% outside air.