Interpretation #7403
Published September 26, 2014
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 4
- Section
- 403.2.1
- Topic
- Outside air requirement
Question
Is it the intent of section 403.2.1 (#3) to require 100% outside air unit for all commercial kitchens?
Answer Published 09/26/2014 at 8:43 AM
No
Commentary
Section 403.2.1, #3 states, "...recirculation from such
spaces shall be prohibited." and, "All air supplied to such
spaces shall be exhausted..." It does not
say "...recirculation within such spaces shall be
prohibited." Nor does it say, "All air supplied within
such spaces shall be exhausted." It is permissible to have
cooling equipment within a kitchen that recirculates air
within that kitchen as long as the required exhaust and
makeup air balance does not result in air being returned to
adjacent spaces. As a corollary, all air being delivered to
the kitchen from an adjacent space must be exhausted simply
because it can't be returned to the adjacent space. It
does not necessarily follow that all the supply needs to be
100% outside air.