Interpretation #7399

Published September 10, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R315.1.1
Topic
CO and Smoke Alarm Interconnection

Question

Is it the intent of R315 to require a hard-wired carbon monoxide alarm to be interconnected with other residential CO or smoke alarms?

Answer Published 09/10/2014 at 4:04 PM

It appears the answer to the question is no.There are 4
methods to meet the carbon monoxide alarm requirement
including battery operated alarms. However, if any
of the smoke/carbon monoxide combo alarms outside the
sleeping rooms are also serving as a required smoke alarm,
they would have to be hardwired to the other smoke alarms.

Commentary

None