Interpretation #7390

Published September 02, 2014

Original Request

Code Version
2010
Code
EXTBLDG
Code Description
Existing Building
Chapter
8
Section
807.4.2
Topic
Truss Over system

Question

Is it the intent of Section 807.4.2 of the Existing Building Code to be used on Interior, Non-Wind Load Framing?

Answer Published 09/02/2014 at 11:23 AM

If, in fact, the existing truss system is completely
disconnected from the structural system of the building,
the provision applies solely to the new truss system. It is
difficult to visualize how the existing system would be
totally disconnected as it would seem there would still be
connection to the exterior walls. If so, while perhaps
interior, the truss may still receive loads due to wind.

Commentary

A structural analysis of the entire assembly may be appropriate as apparently the existing and new engineered components are connected to the exterior walls. Also if the existing trusses are engineered components, any alterations to them may require engineering.