Interpretation #7386

Published August 22, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
9
Section
903.2.7
Topic
Mattresses as upholstered furniture

Question

Is it intended to include mattresses as upholstered furniture?

Answer Published 08/22/2014 at 9:00 AM

No. The common definition
of "upholstered" and the IBC commentary
only extends to furniture such as
chairs and sofas. No mention of the
term "mattress" is used in common
uphholstered furniture definitions or
within the IBC commentary. The term is,
however, included in the 2012 IBC
section 903.2.7, along with an area limitation of 5,000
square feet. So, there was a
conscious decision to include the term
for the 2012 code cycle in this code
section. That would imply mattresses
were not included in the scope of the
2009 base IBC language.

Commentary

Note: In addition, the term "furniture" does not include "mattresses" within the National Fire Incident Reporting System. Mattresses are tracked separately from furniture as an object of fire orgin as the hazard is different. It appears the code has adopted this same approach and consisders furniture and mattresses to be two different hazards.