Is it the intent of section 1609.1.2 exception 1, to restrict wood structural panels used as wind borne debris protection to R3 and R4 occupancies only?
Answer Published 07/25/2014 at 3:47 PM
Yes
Commentary
Other occupancies must meet one of the requirements as
specified in 1609.1.2. The Exception applies solely to R-3
and R-4 occupancies. However, a system may be designed by a
professional engineer using wood structural panels. The
designed engineered system would have to meet all the
requirements of one of the referenced standards. This would
be a local site specific product approval as required by
Rule 9N-3.