Interpretation #7375
Published July 19, 2014
Original Request
- Code Version
- 2010
- Code
- ELECTRIC
- Code Description
- Electrical
- Chapter
- 6
- Section
- 680.25(A)
- Topic
- Panel for pool equipment
Question
Is it the intent of the exception in 680.25(A) to allow a new panel and feeder dedicated for new pool equipment to be connected to an existing remote panel fed by a cable rather than being connected directly to the service panel?
Answer Published 07/19/2014 at 4:51 PM
Yes, provided the cable contains an equipment grounding
conductor the meets the requirements of 250.24(A)(5).
conductor the meets the requirements of 250.24(A)(5).
Commentary
This section has more to do with how it is connected rather
than where it is connected. The electric code has service
conductors (prior to the first means of diconnect), feeders
(between the service diconnect and the branch circuit
(last) overcurrent device panelboard, and branch circuit
conductors (from the final overcurrent device to the
utilization equipment). The feeder, meaning from the last
panelboard containing the branch circuit devices all the
way back to the service must be contain a properly
sized equipment grounding conductor in order to be
utilized. Grounding at the service equipment is
accomplished through bonding to the grounded conductor.