Interpretation #7369

Published July 16, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
507.2.1
Topic
Type 1 hood for wood burning pizza oven

Question

Is it the intent of 507.2.1 to require wood burning pizza ovens be installed under a Type 1 hood?

Answer Published 07/16/2014 at 6:53 AM

Yes

Commentary

A Type I hood is required by code. Wood fired cooking appliances are considered extra-heavy-duty cooking appliances per definition at Section 202.1. Section 507.2.1 requires a Type I hood for extra-heavy-duty- cooking appliances. Further, Section 917.1 requires them to be listed , labeled and installed in accordance with the manufacturer's installation instructions and compliance with UL 2162 Based on the Florida Building Code - Mechanical 2010