Interpretation #7368

Published July 09, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
5
Section
505.1
Topic
Kitchen hood final connection

Question

Is it the intent of section 505.1,when the code section indicates "such ducts shall have smooth inner walls", that the use of flexible and semi- rigid corrugated ducts provided by the manufacturer is allowable under Exception #1 which indicates, "Where installed in accordance with the manufacturer's installation instructions."

Answer Published 07/09/2014 at 1:13 PM

No.

Commentary

FMC 505.1, Exception #1 refers to cases where listed and labeled "recirculating hoods" are used, in such applications hoods are not required to discharge to the outdoors. As long as ventilation to the kichen is in compliance with options provided in Chapter 4