Interpretation #7365

Published July 09, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
3
Section
304.11
Topic
Guardrail for condensor

Question

Is it the intent of section 304.11 that an A/C condenser installation, requires a guardrail if the condenser is installed on a balcony or elevated building structure, and the condenser is 8 feet from the ground and 2 feet from the structure edge, but the structure is not a roof and said not to be considered to be a "walking surface"?

Answer Published 07/09/2014 at 1:02 PM

Yes. However, the balcony or platform would be required to
have a guardrail, too, so a separate guard for the
condenser is not required.

Commentary

None