Interpretation #7361

Published July 09, 2014

Download Final PDF

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
10
Section
1022 -Exit Enclosures
Topic
Fire shutters as "fire barrier"

Question

Is it the intent of the code under 1022.1 to allow for fire shutters to be part of the required "fire barrier" to be constructed in accordance with section 707?

Answer Published 07/09/2014 at 12:59 PM

Probably not. Please see the commentary for additional
information.

Commentary

In addition to 1022, Section 708.7 prohibits penetrations of shaft enclosures other than those necessary for the purpose of the shaft, which in this case is to provide an enclosed exit. Exits may be needed for emergencies other than fire such as hazardous chemical release or other emergencies that would not trigger a fire shutter. Regarding exit passageways, the code limits openings to those necessary for exit access with limited exceptions in malls for mechanical rooms, electrical rooms, building service areas and service elevators. Such penetrations are permitted to open directly into exit passageways, provided the exit passageway is separated from such rooms with not less than 1-hour fire barriers with one hour fire protection in the openings into the exit passageway.