Interpretation #7361
Published July 09, 2014
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 10
- Section
- 1022 -Exit Enclosures
- Topic
- Fire shutters as "fire barrier"
Question
Is it the intent of the code under 1022.1 to allow for fire shutters to be part of the required "fire barrier" to be constructed in accordance with section 707?
Answer Published 07/09/2014 at 12:59 PM
Probably not. Please see the commentary for additional
information.
information.
Commentary
In addition to 1022, Section 708.7 prohibits penetrations
of shaft enclosures other than those necessary for the
purpose of the shaft, which in this case is to provide an
enclosed exit. Exits may be needed for emergencies other
than fire such as hazardous chemical release or other
emergencies that would not trigger a fire shutter.
Regarding exit passageways, the code limits openings to
those necessary for exit access with limited exceptions in
malls for mechanical rooms, electrical rooms, building
service areas and service elevators. Such penetrations are
permitted to open directly into exit passageways, provided
the exit passageway is separated from such rooms with not
less than 1-hour fire barriers with one hour fire
protection in the openings into the exit passageway.