Interpretation #7358
Published July 09, 2014
Original Request
- Code Version
- 2010
- Code
- BUILDING
- Code Description
- Building
- Chapter
- 10
- Section
- 1021.2
- Topic
- Exits from an R-2 Occupancy
Question
Is the intent of table 1021.2 to allow only one exit if the areas served by the single exit do not exceed the limitations of Table 1021.2 and where table 1021.2 appears to limit the number of dwellings to a maximum 4 dwelling units per floor. Or Assuming all other criteria are met, is the intent of 1021.2 to allow as many units per floor as designed as long as no more than the maximum 4 dwelling units are served by one exit.
Answer Published 07/09/2014 at 12:58 PM
Yes
Commentary
The limit is four dwelling units per story; not four
dwelling units served by the exit. While it is true the
text alludes to areas served, it also requires compliance
with Table 1021.2. Table 1021.2 specifically says "dwelling
units per floor" in the column heading and "4 dwelling
units". The table does not say "dwelling units served
by the exit". In the example, 8 units would exceed the
limits of Table 1021.2 and the area served would exceed the
allowances of the table. While not identical, this scenario
is consistent with the requirements of the FFPC s.30.2.4.4.