Interpretation #7355

Published July 01, 2014

Original Request

Code Version
2010
Code
MECHANIC
Code Description
Mechanical
Chapter
3
Section
304.11 Guards
Topic
Guards for fall hazard

Question

Is it the intent of FBC 2010 Mechanical 304.11-

Guards, to be required on top of devices such as

paint spray booths and outside walk-in coolers,

to guard against fall hazards ?

Answer Published 07/01/2014 at 8:56 AM

Maybe. The equipment is probably not the roof, although it
is mounted on the roof. Please see the commentary.

Commentary

The intention is to provide fall protection at the roof edge not the top of the equipment. If the equipment is on the roof and within 10 feet of the roof edge, then the guard rail is required at the edge of the roof not the edge of the top of the spray booth or walk-in freezer.