Interpretation #7349

Published July 01, 2014

Original Request

Code Version
2010
Code
BUILDING
Code Description
Building
Chapter
6
Section
603
Topic
Interior furnishings construction type

Question

Is it the intent of exceptions 6 and 14 to allow for combustible materials to be used for the construction of a skateboard ramp in an existing Type IIB building?

Answer Published 07/01/2014 at 8:49 AM

No.
Exception 6 is limited to small amounts of trim material.

Exception 14 is limited to small amounts of blocking within
walls. Neither of these two scenerios present fire loading
that is consistent with the hazard of a combustible
skateboard ramp.

Commentary

That being said, if the skateboard ramp was constructed out of fire-retardant-treated-wood, it appears that it would potentially be consistent with the fire loading described in exceptions 1.1 or 1.3 and could be permitted with the specific evaluation of an equivalancy by the Building Official. Exception 10, while not specifically referenced in the request, leads to Section 805 which may provide some options.