Interpretation #7345

Published June 24, 2014

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
11
Section
1107.2 &1107.3
Topic
Roof Scuppers

Question

Is it the intent of 1107.2 to not allow the secondary roof drain scupper or drain from a higher roof to spill on to a lower roof?

Answer Published 06/24/2014 at 7:20 PM

The discharge of the upper roof onto the lower roof would

not meet the alert intent of the section.

Commentary

The intent of the Code is to limit the buildup of water on roofs and to alert occupants to a problem. If a higher roof spills onto a lower roof, the alert intent is not met. Use of interior leaders as overflows on the higher roof and discharge at an obtrusive location probably does not meet the intent. The Code calls for discharge above grade, in a location that would normally be observed by the building occupants or maintenance personnel. It is not the intent of the Code to define "normally be observed" as this is up to each designer with acceptance by the AHJ.