Interpretation #7339

Published June 24, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
6
Section
609.1.4
Topic
Wall Grouting

Question

Is it the intent of the Florida Building Code Residential to require that grout placed in lifts exceeding 12'' be consolidated by mechanical means?

Answer Published 06/24/2014 at 7:14 PM

No. Based on Section R609.1.4 Grout placement, five foot

(5') lifts are acceptable, not limited to twelve inches

(12").

Commentary

In addition to lift, grout is also subject to the pour height limitations of Table R609.1.2. There are self- consolidating grouts available that do not require consolidation or re-consolidation. Remember - When referenced standards and the code address a subject and they differ, the code prevails.