Interpretation #7337

Published June 22, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
41
Section
4101.17.1.11
Topic
Screen Used as Child Protection Barrier

Question

Is it the intent of this section to allow the use of a standard screen enclosure, constructed of nylon bug screen only, without any guard provision in the lower 48 inches, to serve as the barrier requirement?

Answer Published 06/22/2014 at 4:04 PM

If the bug screen is part of a screen enclosure, it will

meet the requirements of the child barrier.

Commentary

The code specifically states so. The top of the barrier is typically much higher than 48 inches. The code calls for "at least 48 inches". R4101.17.1.11 Standard screen enclosures which meet the requirements of Section R4101.17 may be utilized as part of or all of the barrier and shall be considered a nondwelling wall. Removable child barriers shall have one end of the barrier nonremovable without the aid of tools.