Interpretation #7333

Published June 22, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
302.3
Topic
Door In Rated Walls

Question

Is it the intent of this section of the code to maintain the fire-resistance rating separations between units by rated wall and floor assemblies only? Would a fire rated door be permitted in the rated wall assembly to interconnect the living spaces of separated dwelling units? There is not a noted code section that would permit or addresses an interconnection of a two family dwelling unit by the installation of a fire rated door.

Answer Published 06/22/2014 at 3:59 PM

No.

Commentary

A door would be permitted. The penetration would have to comply with R302.4.1.1. Seems like an unlikely situation for a two-family dwelling though.