Interpretation #7332
Published June 13, 2014
Original Request
- Code Version
- 2010
- Code
- MECHANIC
- Code Description
- Mechanical
- Chapter
- 6
- Section
- 601.4, Balanced Return
- Topic
- Transfer Ducts
Question
Is it the intent of 2010 FMC, Section 601.4, Exception #1 to apply the 1-1/2 times return duct cross sectional area when using transfer ducts only, or will a ducted return air systems also have to comply with this requirement?
Answer Published 06/13/2014 at 1:55 PM
The exception specifically states "Transfer ducts", so,
this section applies to transfer ducts and not a return air
system.
this section applies to transfer ducts and not a return air
system.
Commentary
A transfer duct is typically not a "forced" air duct and
the sizing should ensure a sufficently low static pressure.
If the air is being pulled by the system this sizing may
not be required, depending on the design of the system.
FBC-M Section 603.2 (and related subsections) deals with
the appropriate methods for sizing of ducts. The AHJ,
if concerned with a specific design/installation, could
require the submission of additional data to substantiate
the design/installation. Further, the AHJ may also require
information on the grille(s) installed to verify they are
installed within the manufacturer's installation
instructions (dealing with acceptable face velocity, etc).
See FBC-M 603.17.