Interpretation #7331

Published June 22, 2014

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
6
Section
602.3.5
Topic
domestic pumps

Question

Is it the intent of of the code to required that domestic pumps and domestic pumping systems conform to NSF 61 as for water distribution "pipe"

Answer Published 06/22/2014 at 3:58 PM

No

Commentary

The section specified applies specifically to pumps used in the water supply. Section 602.3 is intended for on site water supplies. 602.3.5 states the pump shall be "rated for the transport of water." This indicates some type of testing and labeling acceptable to the Code official. Materials used in plumbing systems are called out in Chapter 3, section 303 and Chapter 6, section 605. Further, individual water supplies may include wells per �602.3.1; however, �602.3.5 does not specify a standard for the pump. Section 602.3 requires individual sources of potable water supply to meet the requirements of Ch. 373 FS. Statute calls for wells to comply with FBCP �612 (sic). The section number has changed in FBCP 2010 to �614. Nether statute nor FBCP �614 mention a standard for the pump.