Interpretation #7324

Published April 14, 2014

Original Request

Code Version
2010
Code
PLUMBING
Code Description
Plumbing
Chapter
4
Section
403.1
Topic
Minimum Facilities in Storage Buildings

Question

Is it the intent of FPC403.1 to require each individual storage building on a site to meet the minimum fixture requirement?

Answer Published 04/14/2014 at 6:27 PM

No

Commentary

The facilities may be in a central location, if the travel distance is within the requirements of 403.3.2 (500 ft), and the count meets the minimum of table 403.1. Directional signage would also be required per FBC Plumbing 403.4.1