Interpretation #7322

Published June 22, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R305
Topic
Ceiling Height

Question

1.What is it the intent of R305 regarding the minimum ceiling height of a single family garage? Garage is not identified. 2. What is the intent of the code for the minimum clearance, floor to bottom of the unit for an airhandler installed suspended below a garage ceiling?

Answer Published 06/22/2014 at 3:57 PM

The question needs to be asked as to if this is an existing

building or new construction? The code does not include
garages in the contemplation of non-habitable spaces or the
exceptions to ceiling height requirements. Since the code
does not specifically address garages, but does address
other non-habitable spaces, the code official has some
leeway in making her/his determination.



If this is new construction, the 7' should probably be

applied with a possible reduction to 6' 8" since that

height is allowed in bathrooms and basements, if the

local authority is comfortable with the reduced

height. If it is an existing structure and equipment is

being changed out, the reduced clearance should be

acceptable. Again, this would be a local decision since the

code is silent.

Commentary

1. The definition of habitable space states, in part, "...storage or utility space and similar areas are not considered habitable spaces." A garage would generally fall within this exclusionary portion of the definition of "habitable space" and, therefore, is not considered habitable space. The ceiling height could be 6'8". 2. The Florida Residential Code does not contain a minimum height requirement for an air handler installed in a residential garage, only requirements for protection and installation of the duct