Interpretation #7318

Published March 31, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
R302.11 (4)
Topic
Foam Material for Fireblocking-Penetrations

Question

Is it the intent of R302.11 (4) to use any foam material not rated to prevent fire spread, or does it only need to resist passage of flame?

Answer Published 03/31/2014 at 6:51 PM

No

Commentary

The key to the section is the the words "an approved material", which is intended to block the "free" passage of flame and products of combustion. The section referenced addresses fireblocking in combustible construction. The material does need to resist the free passage of flame as well as smoke and other products of combustion. This is not a "firestop" as would be found in rated construction, but, merely a way of slowing the spread of fire and permitting the flame and products of combustion from communicating freely with other areas. A product acceptable to the designer and the AHJ should be specified on the plans and used for the purpose. The product would be required to provide performance equivalent to any of the seven items listed in Section R302.11.1.