Interpretation #7316

Published March 03, 2014

Download Final PDF

Original Request

Code Version
2010
Code
FUELGAS
Code Description
Fuel Gas
Chapter
4
Section
404.15.3
Topic
marking underground plastic gas pipe

Question

Is it the intent of 404.15.3 to approve the use of conductive foil marking tape for underground plastic pipe. Like it complies with Federal Gas And Safety Regulations 192.321,Osha 1926.956, DOT USAS B31.8,AGA 72-D-56 and NTSB- PSS-73-1?

Answer Published 03/03/2014 at 6:30 PM

No, the intent of this section is to require a tracer to be
installed adjacent to underground nonmetallic piping.

Commentary

The code allows a yellow insulated copper tracer wire or other approved conductor. Approved is defined “Acceptable to the code official or other authority having jurisdiction”. Therefore, to use a material other than a yellow insulated copper tracer wire would first need approval of the Code Official.