Interpretation #7314

Published March 03, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
44
Section
R4403.7.3.6.3
Topic
Interior Stair Railings

Question

Is it the intent of the code for interior stair railings (inside the house communicating first and second floor) on residential (R3) to comply with laminated glazing for HVZ.

Answer Published 03/03/2014 at 6:32 PM

Yes, glazing must be laminated.

Commentary

HVHZ Section R4403.7.3.6.3 allows laminated glazing as a substitute for pickets in railings, stair-railings and other similar safeguards. Clearly, interior stair-rail systems are not subject to wind loads, but must meet the linear and concentrated loads noted. Additionally, it is required that the laminated glazing be tested for kinetic energy impact in accordance with the ANSI Z97.1 test, using the 400 foot-pound procedure. In order to be deemed compliant, laminated glazing subjected to the kinetic energy test must remain in the supporting frame and may not suffer breakage, or allow a shear opening to occur through which a three inch in diameter sphere may freely pass.