Interpretation #7305
Published February 07, 2014
Original Request
- Code Version
- 2010
- Code
- PLUMBING
- Code Description
- Plumbing
- Chapter
- 10
- Section
- 1002.4 Trap Seal
- Topic
- Floor Drain Evaporation Prevention
Question
Is it the intent of Section 1002.4 Trap Seal to require only liquid supplied trap seal devices meeting ASSE 1018 & 1044 to serve floor drains subject to evaporation or are trap seal insert devices acceptable for installation in floor drains to prevent trap evaporation?
Answer Published 02/07/2014 at 6:52 PM
Yes, that is the intent.
Commentary
However, alternate methods or materials may be submitted to
the Building Official for consideration in their
jurisdiction.