Interpretation #7296

Published January 27, 2014

Original Request

Code Version
2010
Code
RESIDENT
Code Description
Residential
Chapter
3
Section
301.2.1.1.2
Topic
Sun Room Classification w/Mini-Split A/C

Question

Is it the intent of the code to classify a sunroom as category IV or V if a mini split unit is installed but only to dehumidify the room?

Answer Published 01/27/2014 at 7:30 PM

Yes

Commentary

A mini split system that could provide cooling added to the sunroom would place the room in category IV or V, depending on thermal isolation or lack thereof from the primary structure. All applicable code requirements would apply. To be exempt, the unit must be controlled by a humidistat only.